| Voltage: | 220 V, 380 V | Protection Class: | Ip56 |
|---|---|---|---|
| Generator Capacity: | 100/125 MW | Generator Rated Voltage: | 10.5 KV |
| Secondary Side Resistance: | 0.5, 0.8, 1 Ω | Maximum Grounding Current: | 4, 5, 6 A |
| Primary Side Voltage: | 10.5/√3, 13.8/√3, 15.75/√3, 18/√3, 20/√3 KV | Secondary Side Voltage: | 0.22 KV |
| Transformer Rated Capacity: | 30, 50 KVA | Grounding Protection Voltage: | 0.1 KV |
| Resistance Temperature Coefficient: | Small | High Temperature Resistance: | Yes |
| Applicable Voltage Range: | 35KV And Below | Resistor Type: | High-voltage Large-power |
| Functional Structure: | Designed For Environment | ||
| Highlight: | 100/125 MW Generator Resistance Cabinet,10.5 KV Neutral Point Grounding Resistance Box,0.5,0.8,1 Ω High Voltage Generator Resistance Cabinet |
||
| Parameter | 100/125 MW | 200 MW | 300 MW |
|---|---|---|---|
| Generator rated voltage (KV) | 10.5 | 13.8 | 15.75 | 18 | 20 |
| Maximum single-phase grounding current (A) | 4 | 5 | 6 |
| Primary side voltage of grounding transformer (KV) | 10.5/√3 | 13.8/√3 | 15.75/√3 | 18/√3 | 20/√3 |
| Secondary side voltage of grounding transformer | 0.22 | 0.22 | 0.22 |
| Rated capacity of grounding transformer (KVA) | 30 | 30 | 50 |
| Secondary side resistance value (Ω) | 1 | 0.8 | 0.5 |
| Grounding protection extraction voltage (KV) | 0.1 | 0.1 | 0.1 |